CFC Free
No Oxygen
Depletion
HFC Free
Certified 15yr Life
Non Pressurized
Zero Ozone
Depletion
Zero Global
Warming
Halon Alternative
Manufactured
under ISO Stds
General FirePro Brochure Product Specifications Control Equipment S D S
Model Weight Discharge
Outlets
Discharge
Time (s)
Activation Modes Dimensions Drawings Data Sheet Product Image
Net (g) Gross (g)
FP-0020S 20 310 2 3-6 Bulb Thermal Activator(BTA) 165mm x 30mm diam. Drawing 0020 Data Sheet 0020 Image 0020
FP-0020SE 20 310 2 3-6 Electrical 165mm x 30mm diam. Drawing 0020 Data Sheet 0020 Image 0020
FP-0040S 40 610 2 5-10 Electrical – or – Bulb Thermal Activator (BTA) 140mm x 50mm diam. Drawing 0040 Data Sheet 0040 Image 0040
FP-0080S 80 870 2 5-10 Electrical – or – Bulb Thermal Activator (BTA) 190mm x 50mm diam. Drawing 0080 Data Sheet 0080 Image 0080
FP-0100S 100 1,370 1 5-10 Electrical – or – Bulb Thermal Activator (BTA) 160mm x 88mm diam. Drawing 0100 Data Sheet 0100 Image 0100
FP-0200S 200 1,840 1 5-10 Electrical – or – Bulb Thermal Activator (BTA) 190mm x 88mm diam. Drawing 0200 Data Sheet 0200 Image 0200
FP-0500S 500 3,340 1 5-10 Electrical – or – Bulb Thermal Activator (BTA) 290mm x 88mm diam. Drawing 0500 Data Sheet 0500 Image 0500
FP-1200 1,200 10,900 1 15-20 Electrical – or – Bulb Thermal Activator (BTA) 216mm x 300mm x 170mm Drawing 1200 Data Sheet 1200 Image 1200
FP-2000 2,000 15,500 1 15-20 Electrical – or – Bulb Thermal Activator (BTA) 300mm x 300mm x 185mm Drawing 2000 Data Sheet 2000 Image 2000
FP-3000 3,000 16,300 1 15-20 Electrical – or – Bulb Thermal Activator (BTA) 300mm x 300mm x 185mm Drawing 3000 Data Sheet 3000 Image 3000
FP-5700 5,700 26,400 1 15-20 Electrical – or – Bulb Thermal Activator (BTA) 300mm x 300mm x 290mm Drawing 5700 Data Sheet 5700 Image 5700
FP-BTA   BULB THERMAL ACTUATOR
Self-contained, automatic and temperature controlled activation system.
Thermal Actuator consists of (a)Thermo Lock with Glass Retort, (b) Spring Transmission of percussive mechanism, which initiates the capsule, (c) Safety Ring and Pin during transportation.
During operation the liquid within the bulb will expand until the required operational temperature is reached. At this point the glass bulb will ‘burst’, allowing the thermal mechanism to actuate the built-in firing pin, which in turn initiates the capsule, and causes ignition of the SBK solid compound in Generator activator.
Precise calibration of the bulbs during production enables accurate operating temperatures to be achieved.
Temp. Ratings (oC)
Temp. Tolerances
Typical Operating Time
79(Yellow), 93(Green), 182(Purple)
± 3.5 %
28 sec (UL)
BTA Assembly BTA Data Sheet
HEAVY DUTY BRACKETS – 316 Stainless Steel
FP-6100 Heavy Duty Bracket
Suits : FP-1200, FP-2000, FP-3000, & FP-5700
Made from Heavy Duty 316 SSteel for Harsh Environments – Marine.

Drawing – 6100

FP-6200 Heavy Duty Bracket
Suits : FP-100, FP-200, and FP-500
Made from Heavy Duty 316 SSteel for Harsh Environments – Marine.

Drawing – 6200 Drawing – 6300