Sigma XT Fire Indicator Panel
Standard AS Fire Panel Warning Signs Local Control Station Thermal Fuse Isolation Switch

Australian Standard Fire Panels are all compatible with FirePro Generators. The Sigma XT panel has a Gas Card to enable delays and warning signs etc. Can operate as a main FIP or Sub FIP and can interface will all types of AS panels.

Warning Signs are an integral part of the Fire System under Australian Standards.
• System Inoperative – WP available
• Fire Alarm – Evacuate Area – WP available
• Fire Alarm – Do Not Enter – WP available

AS 4487-2013 requires a Local Control Station(LCS) if there are multiple entrances to a risk area. An LCS is required at each door. The LCS will has a Manual Activation switch and a Mode Switch built in, as well as mimic indicators from the main panel functions.

Australian Standards require a system activated advice to be sent to the Fire Panel. This is achieved with a thermal fuse which is connected to the FirePro Generators. Connection to the Thermal Fuse is via a Deutsch Plug to allow for easy removal of units should maintenance or access be required.

AS require a monthly test of Systems. This switch allows monthly testing without disruption of connected devices and creates a fault at the panel. We recommend the use of this switch computer servers etc which should not be shutdown during monthly tests.